Once grease vapour leaves the canopy it travels through the exhaust duct, cooling as it goes. That cooling is the problem. Deposits drop out along horizontal runs, collect at bends and settle around joints, building a coating that nobody sees until a panel is opened. In older inner-city buildings the duct may snake through ceilings, risers or neighbouring tenancies before it reaches the roof, which makes it easy to forget about, hard to inspect and difficult to reach without a plan. Fire travels along that coating quickly.
We clean the duct through the access panels already fitted along its route, working from the canopy collar upward and from the fan end downward where that is possible. Deposits are scraped from the walls, collected rather than pushed further along, and the cleaned surfaces are treated with degreaser and wiped back. Long or awkward runs may take more than one access point, and we plan the order of work so nothing loosened in one section ends up resting in the next.
Not every duct can be reached end to end. If a run has no panels for several metres, or passes through spaces we cannot safely enter, we mark it on your notes and photos. That gives you and your building manager a clear starting point if extra access panels are worth installing. It also means the next clean can be planned with realistic expectations, rather than assuming the whole run was covered when it was not.